Rockwell Automation 1799-D12G12GL 12 Input/12 Output Discrete Embedded I/O User Manual

Page 20

Advertising
background image

20

12 Input/12 Output Discrete Embedded TTL I/O Module with Pulse Width Modulation and DeviceLogix

Publication 1799-IN008A-EN-P - July 2005

General Specifications (continued)

EFT/B Immunity

IEC 61000-4-4:

±2kV at 2.5kHz on signal ports

±2kV at 5kHz on communications ports

Surge Transient Immunity

IEC 61000-4-5:

±2kV line-earth (CM) on communications ports

Conducted RF Immunity

IEC 61000-4-6:

10Vrms with 1kHz sine-wave 80%AM from 150kHz...80MHz

Enclosure Type Rating

None (open-style)

5V Supply Voltage Ranges

4.8...5.1V

0...5.1V dc

Supply Power/Current Ratings

Isolated outputs limited to 1 volt-ampere in each ungrounded output
line

Power Consumption

11.25 VA dc

Power Dissipation

11.25 VA dc @ 70

°C, approximate minimum enclosure size 229 mm x

165 mm x 127 mm (9 in. x 6.5 in. x 5 in.)

Isolation Voltage
(continuous-voltage withstand
rating)

50V continuous

Tested to withstand 2000V dc for 60 seconds

Conductors Wire Size

I/O: 20 AWG (0.5mm2)...26 AWG (0.13mm

2

) solid or stranded copper

wire rated at 75 °C or greater 1.2 mm (3/64 in.) insulation maximum.

DeviceNet: 14 AWG (2.5mm

2

)...22 AWG (0.25mm

2

) solid or stranded

copper wire rated at 75 °C or greater 1.2 mm (3/64 in.) insulation
maximum. (Refer to publication DNET-UM072).

Wiring Category

1,2

2 - on signal ports

2 - on communications ports

Wire Type

Copper

1

Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1,

Industrial Automation Wiring and Grounding Guidelines.

2

Use this Conductor Category information for planning conductor routing as described in the appropriate

System Level Installation Manual.