10 FLEX Ex Thermocouple/RTD Input Module

Publication

1797-5.4 - June 2010

Type of Input

Connect the Following

+

H

L

-

Shield

1

RTD - 2-wire

1

2

RTD - 3-wire

1

3

2

RTD - 4-wire

1

1a

2a

2

Thermocouple

1

2

Millivolt

1

2

1Terminals 16, 33, 40…45 are chassis ground.

RTD or

Thermocouple

Channel

RTD Source

Current

(+)

High Signal

Terminal

(H)

Low Signal

Terminal

(L)

Signal

Return

(-)

0

0

1

2

3

1

4

5

6

7

2

8

9

10

11

3

12

13

14

15

4

17

18

19

20

5

21

22

23

24

6

25

26

27

28

7

29

30

31

32

+V

Terminals 34 and 50

-V

Terminals 35 and 51

1 Terminals 37, 38, and 39, and 46, 47, and 48 are for cold junction

compensation (with 38, and 47 chassis ground). Connect CJC1 to
terminal 5 or 22, CJC2 to terminal 12 or 29

2 Terminals 16, 33, and 40…45, are chassis ground.

ATTENTION

Do not use the unused terminals on this terminal base unit.
Using these terminals as supporting terminals can result in
damage to the module and/or unintended operation of your
system.

1

2

3

1a

2a

1

2

1

2

1

2

1

2

2-wire RTD

3-wire RTD

4-wire RTD

Thermocouple

Millivolt