Rockwell Automation 1797-IRT8 FLEX Ex Thermocouple/RTD Module User Manual

Page 19

Advertising
background image

FLEX Ex Thermocouple/RTD Input Module 19

Publication

1797-5.4 - June 2010

Data Organization

Overrange Alarm
Lead Breakage Alarm
Fault State

Sensor Mode RTD 2,
3, or 4-wire,
TC Sensor Type (such as

TC, Type B, E, J..., RTD or
mV
Internal Reference
Junction (TC mode)

Individually for each channel
Individually for each channel
Individually for each channel (includes overrange, lead
breakage and short circuit)
Common to groups of 4 channels (ch 0…3, ch 4…7)

Common to groups of 4 channels (ch 0…3, ch 4…7)

Common to all channels (0 °C, 20 °C, 25 °C, 30 °C, 40 °C, 50
°C, 60 °C, 70 °C selectable

Output (Intrinsically Safe)
(16 Position Male/Female
Flexbus Connector)

U

i

< 5.8V

I

i

< 400 mA

Li = Negligible
Ci < 1.35

F

Isolation Path
Input to Power Supply
Input to Flexbus
Input to Input
Power Supply to Flexbus

Isolation Type
Galvanic to DIN EN60079-11
Galvanic to DIN EN60079-11
None
Galvanic to DIN EN60079-11

Power Supply
(+V, -V Intrinsically Safe)

U

i

< 9.5V dc

I

i

< 1 A

Li = Negligible
Ci = Negligible

Module Field-side Power
Consumption

1.6 W

Power Dissipation

1.6 W

Thermal Dissipation

Max 5.46 BTU/hr

Module Location

Cat. No. 1797-TB3 or 1797-TB3S Terminal Base Unit

Conductor Wire Size

4 mm

2

(12 gauge) stranded max

1.2 mm (3/64in.) insulation max

Dimensions

Metric

Imperial

46 mm x 94 mm x 75 mm

(1.8 in. x 3.7 in. x 2.95 in.)

Weight

200 g (approximate)

Keyswitch Position

2

Specifications continued on next page