28 FLEX Ex Thermocouple/RTD Input Module

Publication

1797-5.4 - June 2010

Table 1

Table 2



The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a
system when the approved values of V

oc

and I

sc

or V

t

and I

t

of the associated

apparatus are less than or equal to V

max

and I

max

of the intrinsically safe

apparatus and the approved values of C

a

and L

a

of the associated apparatus

are greater than C

i

+ C

cable

and L

i

+ L

cable

respectively for the intrinsically safe

apparatus. The internal capacitances Ci of the terminal base must be taken
into account to verify the intrinsic safety.



Simple apparatus is defined as a device which neither generates nor

stores more than 1.2V, 0.1 A, 20 J, or 25 mW.

Wiring

Method

Channel Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

F)

L

a

(mH)

1 and 2

Any one

channel,

for

example,

ch0

0(+), 1(H),

2(L), 3(-)

9.0

37.0

-

-

A, B

3.0

20.0

C, E

9.0

60.0

D, F, G

24.0

160.0

37, 38, 39

(CJC0)

or

46, 47, 48

(CJC1)

9.0

1.0

-

-

A, B

3.0

1000.0

C, E

9.0

1000.0

D, F, G

24.0

1000.0

0(+), 1(H),

2(L), 3(-)

37, 38, 39

(CJC0)

or

46, 47, 48

(CJC1)

-

-

9.0

38.0

A, B

3.0

20.0

C, E

9.0

60.0

D, F, G

24.0

160.0

Terminals

V

t

(V)

I

t

(mA)

Groups

C

a

(

F)

L

a

(

H)

Male Bus

Connector

5.8

400

A-G

3.0

3.0