FLEX Ex Thermocouple/RTD Input Module 9

Publication

1797-5.4 - June 2010

d. Connect the tail of the CJC as follows:
• when using inputs 0 to 3 (row A) only for thermocouple inputs:

connect the tail of CJC1 to terminal 5 and CJC2 to terminal 12 on row

A.

• when using inputs 4 to 7 (row B) only for thermocouple inputs:

connect the tail of CJC1 to terminal 22 and CJC2 to terminal 29 on

row B.

• when using thermocouple inputs 0 to 7: connect the tail of CJC1 to

terminal 5 on row A, and CJC2 to terminal 29 on row B.

3. Connect +V to terminal 34 on the 34 to 51 row (C).

4. Connect -V to terminal 35 on the 34 to 51 row (C).

5. If continuing power to the next terminal base unit, connect a jumper from

terminal 50 (+V) on this base unit to terminal 34 on the next base unit.

6. If continuing common to the next terminal base unit, connect a jumper

from terminal 51 (-V) on this base unit to terminal 35 on the next base

unit.

IMPORTANT

Whenever you use thermocouple inputs, you must use both

cold junction compensators

WARNING

Make certain that you power this module with an intrinsically

safe power supply. Do not exceed the values listed in the

specifications for this module.

If you connect or disconnect wiring while the field-side power is

on, an electrical arc can occur. This could cause an explosion in

hazardous location installations. Be sure that power is removed

or the area is nonhazardous before proceeding.