FLEX Ex Thermocouple/RTD Input Module 23

Publication

1797-5.4 - June 2010

UL, C-UL I/O Entity Parameters

Table 1

Wiring Methods

 Wiring method 1 - Each channel is wired separately.

 Wiring method 2 - Multiple channels in one cable, providing each channel

is separated in accordance with the National Electric Code (NEC) or
Canadian Electric Code (CEC).

Table 2



The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a
system when the approved values of V

t

and I

t

of the associated apparatus are

less than or equal to V

oc

and I

sc

or V

max

and I

max

of the intrinsically safe

apparatus and the approved values of C

a

and L

a

of the associated apparatus

are greater than C

i

+ C

cable

and L

i

+ L

cable

respectively for the intrinsically safe

apparatus.

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

F)

L

a

(mH)

1 and 2

Any one
channel

(for

example,

ch0)

0(+), 1(H),

2(L), 3(-)

9.0

37.0

-

-

A, B

4.9

20.0

C, E

14.7

80.0

D, F, G

39.2

160.0

37, 38, 39

(CJC0)

or

46, 47, 48

(CJC1)

9.0

1.0

-

-

A, B

4.9

1000.0

C, E

14.7

1000.0

D, F, G

39.2

1000.0

0(+), 1(H),

2(L), 3(-)

37, 38, 39

(CJC0)

or

46, 47, 48

(CJC1)

-

-

9.0

38.0

A, B

4.9

20.0

C, E

14.7

80.0

D, F, G

39.2

160.0

Terminals

V

t

(V)

I

t

(mA)

Groups

C

a

(

F)

L

a

(

H)

Male Bus

Connector

5.8

400

A-G

3.0

3.0