14 FLEX Ex Thermocouple/RTD Input Module

Publication

1797-5.4 - June 2010

Output Map

Data Format for All Channels - Write Word 0

Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word

Write

0

Data Format

Flt

Mode

ch

4…7

Flt

Mode

ch

0…3

Reference
Junction

Filter Cutoff

1

TC/RTD

Ch 4…7

Sensor

Mode

ch 4…7

Sensor Type

Ch 4…7

TC/RTD

Ch 0…3

Sensor

Mode

Ch 0…3

Sensor Type

Ch 0…3

2

RTD

Offset

ch 7

RTD

Offset

ch 6

RTD

Offset

ch 5

RTD

Offset

ch 4

RTD Offset

ch 3

RTD Offset

ch 2

RTD

Offset

ch 1

RTD

Offset

ch 0

3

Module command

Module command data

Bit

11

10

09

08

Data type for channels 0…7

0

0

0

0

°C (see note)

0

0

0

1

°F (see note)

0

0

1

0

°K (see note)

0

0

1

1

-32767…+32767

0

1

0

0

0…65535

0101 to 1111 not used

Note: Module defaults to -4000…10,000 in Millivolt mode, and 0…5000 in Ohms mode.