14 FLEX Ex Thermocouple/RTD Input Module
Publication
1797-5.4 - June 2010
Output Map
Data Format for All Channels - Write Word 0
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word
Write
0
Data Format
Flt
Mode
ch
4…7
Flt
Mode
ch
0…3
Reference
Junction
Filter Cutoff
1
TC/RTD
Ch 4…7
Sensor
Mode
ch 4…7
Sensor Type
Ch 4…7
TC/RTD
Ch 0…3
Sensor
Mode
Ch 0…3
Sensor Type
Ch 0…3
2
RTD
Offset
ch 7
RTD
Offset
ch 6
RTD
Offset
ch 5
RTD
Offset
ch 4
RTD Offset
ch 3
RTD Offset
ch 2
RTD
Offset
ch 1
RTD
Offset
ch 0
3
Module command
Module command data
Bit
11
10
09
08
Data type for channels 0…7
0
0
0
0
°C (see note)
0
0
0
1
°F (see note)
0
0
1
0
°K (see note)
0
0
1
1
-32767…+32767
0
1
0
0
0…65535
0101 to 1111 not used
Note: Module defaults to -4000…10,000 in Millivolt mode, and 0…5000 in Ohms mode.