Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual
Page 111

Publication GMSI10-UM013D-EN-P - May 2010
Specifications 101
Non-Volatile Configuration
A copy of the module configuration is
retained in non-volatile memory from where
it is loaded upon power up*.
*The configuration stored in non-volatile
memory can be deleted only by a module-reset
command sent via the serial interface, using
the Serial Configuration Utility, or via
DeviceNet from any compliant software
application.
Accuracy (minimum)
±1% of full scale range for the channel
±1% of alarm setpoint for speed
Power
Module
Consumption
Heat Production
Transducer
+21.6 to +26.4V dc
Maximum: 300 mA
Typical: 175 mA
Maximum: 7 Watts (24 BTU/hr)
Typical: 4 Watts (14 BTU/hr)
Isolated 24V dc, user configurable with
wiring
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Conformal Coating
-20 to +65°C (-4 to +149°F)
-40 to +85°C (-40 to +185°F)
95% non-condensing
All printed circuit boards are conformally
coated in accordance with IPC-A-610C.
Physical
Dimensions
Terminal Screw Torque
Height: 3.8 in (97 mm)
Width: 3.7 in (94 mm)
Depth: 3.7 in (94 mm)
7 pound-inches (0.6 Nm)
XM-122 Technical Specifications
Product Feature
Specification