Transducer dc bias is monitored on all signals, Important – Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual
Page 197

Publication GMSI10-UM013D-EN-P - May 2010
Wiring Connections for Previous Module Revisions 187
Figure D.8 Two IEPE Accelerometers and a Non-Contact Sensor Wiring
IMPORTANT
The module’s 24 V power supply (terminal 25) is providing
24 V power to the IEPE accelerometer constant current
diodes. Refer to Appendix A for power specifications.
Make certain the IEPE Power parameter is enabled for
both channel 1 and channel 2. Refer to Channel Transducer
Parameters on page 58.
IMPORTANT
Transducer DC bias is monitored on all signals.
TYPICAL WIRING FOR TWO IEPE ACCELEROMETERS AND
NON-CONTACT SENSOR TO XM-122 VIBRATION MODULE
Shield
Pin A - Signal
Pin B - Common
Cable shield not
connected at this end