Installing the XM-122 gSE Vibration Module 37
Figure 2.26 DC Voltage Signal to Channel 2 Wiring
Connecting an IEPE Accelerometer and Non-Contact Sensor
Figure 2.27 shows the wiring of an IEPE accelerometer to channel 1 and the
wiring of a non-contact sensor to channel 2.
TYPICAL WIRING FOR PROCESS DC VOLTAGE SIGNAL
TO XM-122 VIBRATION MODULE CHANNEL 2
Cable shield not
connected at this end
Shield
1
17
Channel 2 Input Signal
Signal Common
38
Process DC
Source
ATTENTION
Figure 2.27 shows the wiring to the XM-122 module
revision D01 (and later). Earlier revisions of the module do
not support this wiring configuration. Refer to Appendix
D for information about wiring earlier revisions.
ATTENTION
You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield at the terminal base
and not at the transducer. Any convenient Chassis terminal
may be used (see Terminal Block Assignments on page 18).
IMPORTANT
Make certain the IEPE Power parameter for channel 1 is
enabled so power is provided to the accelerometer. Refer
to Channel Transducer Parameters on page 58.