RTD Input Equipment (T3432)
 
1 2  
Industrial Control Services
Figure 9. Selecting American or European Type RTDs.
Selecting 2, 3 or 4-wire RTD Input Lead Configuration.
To select the lead configuration for the RTDs, position the 
jumper for each group as illustrated in Figure 10. The jumper 
posts are labeled “JP7” for group 1 inputs and “JP8” for group 
2 inputs. 
2-wire lead configuration is configured the same as 4-wire lead 
configuration. 
Figure 10. Selecting 2, 3, or 4-Wire Lead Configuration.
RTD Current Source
The RTD termination panel has sixteen current sources that 
power each of the RTD inputs. Termination panels are 
provided with standard 1mA current sources. Optionally, 5mA 
current sources are available, but must be special ordered. 
For most applications, the standard 1mA current sources are 
recommended. 
Two sets of jumper posts are located on the multiplexer to 
indicate the type of current sources installed. These jumper 
posts are labeled “JP1” and “JP9” and must be configured for 
the same type of current sources. Position the jumper on the 
Note: