1. For unused input channels, short the +SENSE, -SENSE,
and -FORCE terminals together. This will eliminate any 
floating readings for the unused channels. 
2. Minimize the resistance of the RTD extension wire by
using heavier wire gauges. The RTD input circuit supports 
a maximum 20 Ohms lead resistance. 
Radiated Field Susceptibility
Transmitting equipment should not be operated within the 
vicinity of the termination panel. Power levels greater than 
one watt at a distance of one foot may degrade RTD 
measurements and eventually cause a permanent fault to be 
logged, resulting in a shutdown (clear to 0) of all inputs on the 
affected panel. 
Grounding
The termination panel should be connected to the system’s 
safety or system ground. Use a minimum of #18 stranded 
wire. A chassis ground terminal is provided for this purpose. 
It is located at the bottom right corner of the termination 
panel, near RTD input 16. 
Additional ground terminals are provided with each RTD 
terminal block group. These terminals are electrically 
connected to the chassis and can be used for RTD field cable 
shield terminations. 
Installing the Termination Panel
The RTD termination panel can be mounted in a 19-inch rack 
or flush mounted to a panel. Refer to Figure 14 for overall 
mounting dimensions for the termination panel and Mux.