RTD Input Equipment (T3432)
 
P D - 6 0 3 7 M a r - 0 6  
7
Termination Panel and Multiplexer
Figure 4 shows the physical features of the RTD termination 
panel and multiplexer. The multiplexer plugs into the 
termination panel and is secured in place with two thumb 
screws located at each end of the multiplexer. Up to three 
multiplexers can be installed in a single termination panel. 
Each multiplexer interfaces to a separate RTD input module 
installed in an I/O Chassis. 
Sixteen current sources are installed on the termination panel 
to source current to each RTD. The current sources are 
powered from the installed multiplexers and share power 
when multiple multiplexers are installed. 
Termination cables plug into the DB-9 connectors located to 
the right of the three multiplexers. Each cable interfaces one 
multiplexer to its associated input module installed in an I/O 
chassis. 
RTD inputs are wired to the terminal blocks located along the 
bottom of the termination panel. Each of the four terminal 
blocks has screw terminals for 4 RTD inputs. Four screw 
terminals are provided for each RTD input. Two additional 
ground terminals on each terminal block are provided to 
connect RTD cable shield wires if desired. 
RTD Multiplexer Indicators
Each RTD multiplexer has status indicators for power supply 
voltages, and transmit data. When positive and negative 
supply voltages are present at the termination panel, the + V, 
and – V indicators are on. The TX indicator is on when the 
Mux is transmitting data to the input module. Normally, all 
these green indicators should be on.