Rtd terminations – Rockwell Automation T3432-CA ICS Regent RTD Input Equipment User Manual
Page 19
                                    Advertising
                                    
                                        
                                    
                                
                                 
RTD Input Equipment (T3432)
 
P D - 6 0 3 7 M a r - 0 6  
19
RTD Terminations
RTD wiring is connected to the screw terminals located at the 
bottom of the termination panel as shown in Figure 16. When 
terminating RTD wiring, follow the recommendations listed 
below. 
1. Greater accuracy is maintained with a heavier gauge RTD
lead wire. Lead wire resistance should not exceed 
20 Ohms. 
2. All RTDs within a group of eight must be the same RTD
type (American or European) and use the same number of 
leads (2, 3 or 4-wire). 2-wire and 4-wire RTDs can be mixed 
in the same group. 
3. For unused RTD inputs, short the +SENSE, -SENSE, and
-FORCE terminals together.