Fault tolerant configurations – Rockwell Automation T3432-CA ICS Regent RTD Input Equipment User Manual
Page 9
 
RTD Input Equipment (T3432)
 
P D - 6 0 3 7 M a r - 0 6  
9
Figure 5. Simplex RTD Input Configuration.
Fault Tolerant Configurations
For safety-critical inputs, redundant input modules and 
multiplexers are used in a 2oo3 or 1oo2 fault tolerant 
configuration. In these configurations the redundant RTD 
input equipment is connected to single or multiple RTDs. 
When single RTDs are installed in the field, the RTDs connect 
to one termination panel containing redundant multiplexers 
which interface to redundant input modules as illustrated in 
Figure 6. When redundant RTDs that sense the same process 
variable are installed in the field, each RTD connects to one 
termination panel, multiplexer and input module as 
illustrated in Figure 7. Each RTD input module, cable, and 
multiplexer is hot replaceable. In redundant input 
configurations, if a fault occurs in one set of equipment, the 
failed equipment can be removed and replaced while the 
system continues to sense the inputs from the remaining two 
sets of equipment.