RTD Input Equipment (T3432)
 
1 4  
Industrial Control Services
Position the jumper on the posts as illustrated in Figure 13 for 
the desired temperature units. 
The temperature data resolution must also be configured for 
units (data increments of 1 degree), or tenths (data increments 
of 0.1 degree). Position the jumper on the posts as illustrated 
in Figure 13 for the desired data resolution. 
The RTD data is always presented as integer data to the 
processor modules. When you select tenths resolution, there 
is an implied fixed place decimal before the least significant 
digit in the temperature data. For example the temperature 
data value 1527 would represent 152.7º. 
The RTD data format selections apply to all 16 RTD inputs.
Figure 13. Selecting RTD Data Format.
The ranges of temperature data for RTDs are shown in 
Table 1. When the temperature data is outside the normal 
operating range, the NOSIG bit is set. 