10 XM Dynamic Measurement Module Terminal Base

Publication

ICM-IN003D-EN-P - March 2013

DIN Rail Grounding Block

24V Common Grounding

The XM system is sourced by a single Class 2 power supply. We recommend
grounding the 24V power to the XM modules.

Transducer Grounding

Be sure that the transducers are electrically isolated from earth ground. Cable
shields must be grounded at one end of the cable, and the other end left
floating or not connected. Where possible, ground the cable shield to the XM
terminal base (Functional Earth terminal) and not at the transducer.

To Earth Ground

8.4 mm² (AWG 8) Wire

Din Rail Grounding Block