Terminating resistors – Rockwell Automation 1440-TBS-J XM Dynamic Measurement Module Terminal Base User Manual

Page 11

Advertising
background image

XM Dynamic Measurement Module Terminal Base 11

Publication

ICM-IN003D-EN-P - March 2013

Terminating Resistors

The XM Bus operates correctly when there is a terminating resistor at each
end of the XM Bus:

Terminating resistors must be 121Ω, 1%, 1/4 W.

When installing the XM ControlNet adapter with XM modules, the
ControlNet adapter has an internal terminating resistor. The other
terminating resistor must be installed at the opposite end of the bus.

A second terminating resistor is installed across the CAN_High and
CAN_Low terminals of the XM module at the other end of the XM
Bus.

Refer to Terminal Assignments on page 16

.

31865

24 V

24 V COM

Supply

XM

®

XM

®

24 V COM

24 V

1

1

1

1

1

1

1

CAN HIGH

BUS V -

DRAIN WIRE

CAN LOW

Termination

resistor

121 ohm, 1%,

1/4W

Class 2