20 XM Dynamic Measurement Module Terminal Base

Publication

ICM-IN003D-EN-P - March 2013

Surge Transient Immunity
IEC 61000-4-5:

±1 kV line-line (DM) and ±2 kV line-earth
(CM) on power ports
±1 kV line-line (DM) and ±2 kV line-earth
(CM) on signal ports
±2 kV line-earth (CM) on shielded ports

Conducted RF Immunity
IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM
from 150 kHz…80 MHz

Certifications

Certifications

(1)

(when product is marked)

Description

c-UL-us

UL Listed Industrial Control Equipment, certified for US and
Canada. See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File
E194810.

CE

European Union 2004/108/EC EMC Directive, compliant
with:

EN 61326-1; Meas./Control/Lab., Industrial
Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8,
Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with:

EN 60079-15; Potentially Explosive Atmospheres,
Protection "n" (II 3 G Ex nA IIC T4X Gc)

EN 60079-0; General Requirements (Zone 2)

Environmental Specifications

Attribute

Value