Specifications – Rockwell Automation 1440-TBS-J XM Dynamic Measurement Module Terminal Base User Manual
Page 18

18 XM Dynamic Measurement Module Terminal Base
Publication
ICM-IN003D-EN-P - March 2013
Specifications
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication
XM Dynamic Measurement Terminal Base - 1440-TBS-J
Attribute
Value
Enclosure Type Rating
None (open-style)
Isolation Voltage
Established by installed module
Voltage Ratings
XM Bus
Power Terminals
I/O Terminals
24V DC, 3 A max, Class 2/SELV/PELV
24V DC, 3 A, Class 2/SELV/PELV
24V DC, 60 mA, Class 2/SELV/PELV
Wire Size
0.34... 2.1 mm
2
(22...14 AWG) solid or
stranded copper wire rated at 75 °C
(167 °F) or greater, 1.2 mm (3/64 in.)
insulation max, recommended strip length
8 mm (0.31 in.)
Wiring Category
(1)
Established by installed module
North American Temp Code
T5
IEC Temp Code
T4
Environmental Specifications
Attribute
Value
Operating temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal
Shock):
-20…70 °C (-4…158 °F)
Temperature, surrounding air, max
70 °C (158 °F)