Before You Begin

To effectively use the terminal base, note the following considerations.

Power Requirements

Use a single Class 2 power supply to power the XM modules. Total current
draw through the side connector cannot exceed 3 A. Refer to the specification
for the specific modules for power requirements.

XM Modules with Separate Power Connections

ATTENTION

To comply with the CE Low Voltage Directive (LVD), all connections to this
equipment must be powered from a source compliant with the following:
safety extra low voltage (SELV) or protected extra low voltage (PELV).

ATTENTION

Multiple power sources are not allowed.

31865

24 V

24 V COM

Supply

XM

®

XM

®

24 V COM

24 V

1

1

1

1

1

1

1

CAN HIGH

BUS V -

DRAIN WIRE

CAN LOW

Termination

resistor

121 ohm, 1%,

1/4W

Class 2