T6050 Hardware & Installation Guide

Chapter 4 – Installation

PD-6050 Dec 04

7

Chapter 4 - Installation

Site Selection Considerations

The T6050 requires the following conditions during normal operation:

32 to 130ºF (0 to 55ºC)

5 to 96% relative humidity

Protection from direct contact with water, chemicals, and conductive dust

Limited exposure to sulfur compounds, acid other corrosive or reactive vapors or fumes,
and conductive dust

Limited exposure to non-conductive dust and combustible dust and lint

Access Considerations

There are very few restrictions on the mounting position of the T6050. The following should be
taken into consideration:

All input/outputs are connected on the termination type electronic component housing.
Adequate wireway space should be provided.

Outdoor installation is not recommended, but can be accomplished if the module is
placed in an appropriate enclosure.