Chapter 5 - specifications – Rockwell Automation T6050 SurgeGard Incipient Surge-Conditioning Module User Manual

Page 23

Advertising
background image

T6050 Hardware & Installation Guide

Chapter 5 – Specifications

PD-6050 Dec 04

13

Chapter 5 - Specifications

Analog Input

Signal Types

-10 - +10 V, 0-5 or 1-5 VDC; 0-20 or 4-20 mA
(with jumper installed across terminals 3 and 4)

Input Frequency

0-20 Hz

Isolation

+/- 15 VDC continuous

Common Mode Rejection

80 db min at 60 Hz peak input; +/- 10 VDC max

Maximum Input Voltage Range

+/- 10 VDC operating, non-destructive

Transmitter Type

2- or 4-wire; transmitter excitation supplied from external source

Input Filtering

differential input band pass (1Hz to 10Hz) amplifier/filter,

A low pass filter (10Hz), absolute-value, peak detector

Analog Output

Signal Type

4-20 mA two-wire loop powered

Load Resistance

<600 ohms

Accuracy

+/- 2 % of full scale

Ripple

± 100 mV maximum

Power Source

22-32 VDC loop powered externally supplied

Analog AC Signal Output

Signal Type

Filtered, Amplified AC Signal; 0-7 V peak-to-peak, based upon

Analog Input Amplitude, Frequency and Gain Setting

Power Requirements

Loop Powered

22-32 VDC two-wire loop powered through Analog Output

Current Requirements

45 mA surge maximum at power up, 2 mA + Analog Output
Value (20 mA maximum) equals 22 mA maximum after power
up

Power Requirements

1.44 watts surge maximum at power up, 0.7 watts maximum
after power up