Appendix I

Deltabar S Differential Pressure

This example shows the level measurement with Deltabar S.

Measured Variable

Differential pressure, from which flow (volume or mass current) and level (level,
volume or mass) are derived.

Signals from Instrument to Control System

h = Δ

p

ρ g

+

+

h

Item

Description

1

Level measurement via impulse piping and PMD70

2

Level measurement with FMD76

3

Level measurement with FMD78

h

Height (level)

p

Differential pressure
Density of the medium

g

Gravitation constant

Signal

Details

Output signal

4...20 mA with superimposed digital communication protocol HART 5.0, 2-wire

Signal range

4...20 mA HART
3.8 mA to 20.5 mA

Signal on alarm

4...20 mA HART

Options
Max. alarm*: can be set from 21...23 mA
Keep measured value: last measured value is kept
Min. alarm: 3.6 mA
*Factory setting: 22 mA