Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014

Appendix A

Promag 53 Electromagnetic Flowmeter

Measured Variable

Flow rate (proportional to induced voltage)

Signals from Instrument to Control System

Connect a Promag 53
Flowmeter

Use a 4-wire connection to the HART input module.

1. Remove the cover of the connection compartment (f ) from the

transmitter housing.

2. Feed the power supply cable (a) and signal cables (b) through the

appropriate cable entries.

Item

Description

Ue

Induced voltage,

Ue = B· L· v

B

Magnetic induction (magnetic field)

L

Electrode gap

V

Flow velocity

Q

Volume flow,

Q = A· v

A

Pipe cross-section

I

Current strength

Signal

Details

Current Output

Active/passive selectable, galvanically isolated
Active: 0/4...20 mA, RL < 700

Ω (HART: RL ≥ 250 Ω)

Passive: 4...20 mA, operating voltage VS 18...30V DC, Ri

< 150 Ω

Pulse/Frequency Output

Active/passive selectable, galvanically isolated (Ex i version: only passive)
Active: 24 V DC, 25 mA (max. 250 mA during 20 ms), RL > 100

Ω

Passive: open collector, 30V DC, 250 mA
Frequency output: full scale frequency 2...10000 Hz (fmax = 12500 Hz), EEx-ia: 2...5000 Hz; on/off ratio 1:1;

pulse width max. 10 s

Pulse output: pulse value and pulse polarity adjustable, pulse width configurable (0.05...2000 ms)