Connect a proline t-mass 65 flowmeter – Rockwell Automation 1734sc-IE4CH E+H Instruments via HART to PlantPAx User Manual User Manual

Page 91

Advertising
background image

Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014

91

Proline t-mass 65 Thermal Flowmeter

Appendix B

Connect a Proline t-mass 65
Flowmeter

Use a 4-wire connection to the HART input module.

1. Unscrew the connection compartment cover (f ) from the transmitter

housing.

2. Feed the power supply cable (a) and the signal cable (b) through the

appropriate cable entries.

3. Connect the HART communications cable to the HART connector in

the order white (+), black (-) on pins 26, 27 of the connector.

4. For AC powered instruments, connect the AC cable to the power

connector in the order ground (as shown), black (pin 1), white (pin 2).

5. Screw the cover of the connection compartment (f ) back onto the

transmitter housing.

Item

Description

a

Cable for power supply: 85...260 V AC, 20...55 V AC, 16...62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L- for DC

b

Signal cable: Terminals Nos. 20-27

c

Ground terminal for protective earth

d

Ground terminal for signal cable shield

e

Service adapter for connecting service interface FXA193 (FieldCheck, FieldCare)

f

Cover of the connection compartment

g

Securing clamp

b

b

c

d

a

a

2
1

– 27

– 25

– 23

– 21

+ 26

+ 24

+ 22

+ 20

L1 (L+)

N (L-)

g

f

e