Connect a liquiline m cm42 transmitter, Housing grounding, Stainless steel housing – Rockwell Automation 1734sc-IE4CH E+H Instruments via HART to PlantPAx User Manual User Manual

Page 150: Housing grounding stainless steel housing

Advertising
background image

150

Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014

Appendix M

Liquiline M CM42 Transmitter

Connect a Liquiline M CM42
Transmitter

Use a 2-wire connection to the HART input module.

Housing Grounding

You must connect the “Fixing plate” to the foundation ground with a separate
functional ground line (2.5 mm2 i14 AWG).

Stainless Steel Housing

You must connect the outer ground connection of the housing to the foundation
ground with a separate line (GN/YE) (

≥ 2.5 mm2 i14 AWG).

Item

Description

1

Fixing plate

2

2.5 mm2 (i14 AWG) functional ground

Item

Description

1

Outer ground connection

2

2.5 mm2 (i14 AWG) line (GN / YE)