4.1.3. MCB discrimination

MCB discrimination studies should be carried out when designing the system power distribution.

Figure 8 Power pack (s) severe overload Current v Time

The graph above shows the response of a single power module to severe overloads. As the load is
increased the power supply protection mechanism operates and shuts down the output. It can be seen
that for a period of just in excess of 200mS the Power module can provide currents up to 115Amps or
380% of its stated maximum(115/31 = 3.8). This 200mS/380% can be extrapolated for additional
power supplies in order to perform MCB discrimination studies.

Power Unit(s) Overload Current Vs Time

0

50

100

150

200

250

300

0

20

40

60

80

100

120

140

Current / Amps

T

im

e

/

m

s

1 Power Unit
2 Power Units