5.2. Circuit Description

The circuit is split into four functional sections: supply, dc alarms, ac alarms and jumpers.

5.2.1. Supply

The 24V supply is connected to CON3 pins 1 & 6. The supply should be fused close to its source,
using a 500mA F rated fuse. It is nevertheless protected by a non-replaceable fuse on the Power Port.
The 24V is regulated down to 5V with decoupling provided. The 5V+ is used to supply the low voltage
electronics. The 24V is used to supply the relays and is connected through the CON2 to power the
optional Power Controller.

5.2.2. DC Alarms

CON1 is the 25 way D male interface to the Power Shelf. The Power Pack and Power Shelf alarm
outputs are derived from here. There are two dc alarms per Power Pack: DCFAIL (dc output fail) and
OTP (over-temperature protection). The Power Port OR’s together DCFAIL and OTP to give one DC
fail alarm, via CON 3. If either alarm triggers, the corresponding relay de-energises.

Each relay operates a volt free contact. These are closed when healthy (relay energised) and open in
alarm. The contacts share a common return line.

5.2.3. AC Alarms

In a similar manner, each Power Pack generates an AC alarm. When an alarm is triggered, the
corresponding relay de-energises. Each relay operates a volt free contact. These are closed when
healthy (relay energised) and open in alarm. The contacts share a common return line.

Fault Condition

Output OK LED

OTP Alarm

AC Fail alarm

dc Fail alarm

dc Output

No fault

Green

Low

Closed

Closed

ON

Fan locked rotor

Amber

Low

Closed

Closed

OFF

Secondary over
temperature

Amber

High

Closed

Open

OFF

Primary over
temperature

Off

High

Closed

Open

OFF

AC Feeder Fail

Off

Low

Open

Open

OFF

Table 7 Alarm Conditions