Environmental characteristics, Figure 9 operation derating curve, Table 6 environmental characteristics – Rockwell Automation T823X Trusted Power System User Manual
Page 21: Trusted, Power system t823x

Trusted
TM
Power System T823X
Issue 9 Dec 08
PD-T823X
21
4.6. Environmental Characteristics
Parameter
Min
Typ
Max
Unit Note
Storage Temperature
-40
-85
°C
Operating
Temperature (note 1)
0
-
60
°C 1. Derate at 1.333%/°C, 45°C to 50°C 2.
Derate at 4.667%/°C, 50°C to 60°C
Acoustics
47
52
dBa Sound Pressure Level at 1m
Humidity (non-
condensing)
5
95
%
Altitude
-60
3962
m
Derated at 2°C/304m above 2438m.
Electro Static
Discharge
IEC1000-4-2 Level 3 stand-alone
Electromagnetic
Immunity (error free)
IEC1000-4-3 Level 2 stand-alone
Isolation Voltage
3,000
1,500
1,500
VAC
VAC
VAC
Primary to Secondary
Primary to chassis GND,
Secondary to chassis GND
MTBF
4 x 10
5
hours @110Vinput 80% load, T
A
= 30
o
C
Vibration
Meet IEC68-2-6
Shock
Meet IEC68-2-36
Weight
2.3
kg
Table 6 Environmental Characteristics
Figure 9 Operation Derating Curve