Environmental characteristics, Figure 9 operation derating curve, Table 6 environmental characteristics – Rockwell Automation T823X Trusted Power System User Manual

Page 21: Trusted, Power system t823x

Advertising
background image

Trusted

TM

Power System T823X

Issue 9 Dec 08

PD-T823X

21

4.6. Environmental Characteristics

Parameter

Min

Typ

Max

Unit Note

Storage Temperature

-40

-85

°C

Operating
Temperature (note 1)

0

-

60

°C 1. Derate at 1.333%/°C, 45°C to 50°C 2.

Derate at 4.667%/°C, 50°C to 60°C

Acoustics

47

52

dBa Sound Pressure Level at 1m

Humidity (non-
condensing)

5

95

%

Altitude

-60

3962

m

Derated at 2°C/304m above 2438m.

Electro Static
Discharge

IEC1000-4-2 Level 3 stand-alone

Electromagnetic
Immunity (error free)

IEC1000-4-3 Level 2 stand-alone

Isolation Voltage

3,000
1,500
1,500

VAC
VAC
VAC

Primary to Secondary
Primary to chassis GND,
Secondary to chassis GND

MTBF

4 x 10

5

hours @110Vinput 80% load, T

A

= 30

o

C

Vibration

Meet IEC68-2-6

Shock

Meet IEC68-2-36

Weight

2.3

kg

Table 6 Environmental Characteristics

Figure 9 Operation Derating Curve

Advertising