Input specification, Line harmonics, Table 3 input specification – Rockwell Automation T823X Trusted Power System User Manual

Page 18: Trusted, Power system t823x

Advertising
background image

Trusted

TM

Power System T823X

Issue 9 Dec 08

PD-T823X

18

4.2. Input Specification

Parameter

Min

Typ

Max

Unit

Condition

Input voltage

90

264

Vac

Input Frequency

47

63

Hz

Inrush Current (peak) per pack

50

<25

A
A

Full load
No load

Input current

0.2

A

No load

Power Factor

0.95

0.99

> 50% of full load

Input Leakage Current

1.7

mA

264Vac, 50Hz

Lighting Surge & Transients
(damage free operation)

IEC1000-4-5 Level 3
IEC1000-4-4 Level 3

Hold Up Time

20

mS

At 600W

EMC (conducted)

CISPR22 Class B,
EN55022 Class B, with 3dB
margin

Table 3 Input Specification

4.3. Line Harmonics

Active power-factor correction circuitry ensures that this Power Pack meets the requirements of
IEC1000-3-2.

Advertising