Input specification, Line harmonics, Table 3 input specification – Rockwell Automation T823X Trusted Power System User Manual
Page 18: Trusted, Power system t823x
Advertising
![background image](/manuals/581185/18/background.png)
Trusted
TM
Power System T823X
Issue 9 Dec 08
PD-T823X
18
4.2. Input Specification
Parameter
Min
Typ
Max
Unit
Condition
Input voltage
90
264
Vac
Input Frequency
47
63
Hz
Inrush Current (peak) per pack
50
<25
A
A
Full load
No load
Input current
0.2
A
No load
Power Factor
0.95
0.99
> 50% of full load
Input Leakage Current
1.7
mA
264Vac, 50Hz
Lighting Surge & Transients
(damage free operation)
IEC1000-4-5 Level 3
IEC1000-4-4 Level 3
Hold Up Time
20
mS
At 600W
EMC (conducted)
CISPR22 Class B,
EN55022 Class B, with 3dB
margin
Table 3 Input Specification
4.3. Line Harmonics
Active power-factor correction circuitry ensures that this Power Pack meets the requirements of
IEC1000-3-2.
Advertising