Trusted, Power system t823x – Rockwell Automation T823X Trusted Power System User Manual

Page 19

Advertising
background image

Trusted

TM

Power System T823X

Issue 9 Dec 08

PD-T823X

19

4.4. Efficiency and Power Factor vs. Input Voltage at Full Load

Input

voltage

Efficiency

(Typical)

Power Factor (Typical)

90Vac

78%

0.99

100Vac

79%

0.99

110Vac

80%

0.99

120Vac

81%

0.98

180Vac

82%

0.98

220Vac

83%

0.98

240Vac

83%

0.98

264Vac

84%

0.98

Table 4 Efficiency and Power Factor vs. Input Voltage at Full Load

When using this table to calculate cable feed requirements, allow, at a minimum, an extra 3% for
variations between units. Actual measured results will depend upon the harmonic content of the input
voltage waveform.

Advertising