5.2.4. Jumpers

There are three jumpers, J1, J2 and J3.

J1 and J2 set the Power Shelf address lines for the I

2

C control bus. With J1 and J2 fitted the Pack

addresses are 1, 2 and 3, which is the default. Other addresses may be set by removing one or both of
J1 and J2, up to 4 shelves worth (or 12 Power Packs).

Power Shelf

J1

J2

1

fitted

fitted

2

fitted

removed

3

removed

fitted

4

removed

removed

Table 8 Power Shelf Addressing

J3 connects together the common return lines of the DC alarms and AC alarms. J3 is fitted by default.