Application, Module configuration, T8449 complex equipment definition – Rockwell Automation T8449 Trusted TMR 24V dc Valve Monitor Module - 40 Channel User Manual

Page 22: Table 3 complex equipment definition, Trusted, Module t8449

Advertising
background image

Trusted

TM

Module T8449

Issue 13 Apr 10

PD-T8449

22

3. Application

3.1. Module Configuration

There is no configuration required to the physical output module. All configurable characteristics of the
module are performed using tools on the EWS and become part of the application or system.ini file
that is loaded into the TMR Processor. The TMR Processor automatically configures the output
module after applications are downloaded and during Active/Standby changeover.

The

IEC1131 TOOLSET

provides the main interface to configure the output module. Details of the

configuration tools and configuration sequence is provided in PD-8082B. There are three procedures
necessary to configure the output module. These are:

1. Define the necessary I/O variables for the field output data and module status data using the

Dictionary Editor of the

IEC1131 TOOLSET

.

2. Create an I/O module definition in the I/O Connection Editor for each I/O module. The I/O

module definition defines physical information, e.g. Chassis and Slot location, and allows
variables to be connected to the I/O channels of the module.

3. Using the Trusted

TM

System Configuration Manager, define custom LED indicator modes,

per-channel shutdown states, and other module settings.

3.2. T8449 Complex Equipment Definition

The T8449 I/O Complex Equipment Definition includes 8 I/O boards, referenced numerically by Rack
number:

Rack I/O Board

Description

Data
Type

Direction

No. of
Channels

OEM Parameters

-

-

-

1

DO_TEST

Output Command / Test Command

Boolean

Out

40

2

STATE

Field Output State

Integer

In

40

3

AI _MXIN

Output voltage / MUX data selection Integer

In

40

4

CI _MXDAT

Output current / MUX data

Integer

In

40

5

MXOUT

MUX data request

Integer

Out

20

6

ETM_EST

Max Test Time / Test End State

Integer

Out

40

7

LINEFLT

Line Fault Status

Boolean

In

40

8

DISCREP

Channel Discrepancy

Integer

In

3

9

HKEEPING

Housekeeping Registers

Integer

In

57

10

INFO

I/O Module Information

Integer

In

11

Table 3 Complex Equipment Definition

Advertising