Trusted

TM

Module T8449

Issue 13 Apr 10

PD-T8449

28

3.2.6. Rack 6: ETM_EST

This board provides connections to the ETIME and ESTATE signals for each field device.

Channel

Field
Device

Description

1

End Time for valve test

2

1

End State for valve test

3

End Time for valve test

4

2

End State for valve test

39

End Time for valve test

40

20

End State for valve test

Table 12 rack 6: ETM_EST descriptions

The ETIME signal is used to specify the maximum amount of time that a valve test is allowed to
continue before returning the valve to its commanded state. ETIME is specified in milliseconds, and
may be any value between 0 and 32767. Values outside the valid range will be set to 0. Because a
non-zero value (i.e. 1 < value < 32767) must be specified before a value test can be initiated, setting
ETIME to 0 inhibits valve testing.

The ESTATE signal is used to specify the desired end state for the feedback input for a valve test. The
possible end states correspond to the values reported for feedback input state on the State board
(Rack 2) and must be between 0 and 6. Values outside the valid range will be set to 0. Because a non-
zero value (i.e. 1 < value < 6) must be specified before a valve test can be initiated, setting ESTATE to
0 inhibits valve testing.

Both ESTATE and ETIME are sampled by the module when it detects a rising edge on the TEST signal
(Rack 1). Changes to ETIME or ESTATE during a valve test are valid, but will not go into effect until
the start of the next valve test (i.e. on the next rising edge of the TEST signal).