Table 20 rack 10: valve test state descriptions, Trusted, Module t8449 – Rockwell Automation T8449 Trusted TMR 24V dc Valve Monitor Module - 40 Channel User Manual

Page 34

Advertising
background image

Trusted

TM

Module T8449

Issue 13 Apr 10

PD-T8449

34

Valve Test State is used to report the state of the valve test that is in progress. Valve Test State is an
integer, with the following valid values:

Value State

Description

0

Idle

There is no valve test in progress.

1

Test In
Progress

A valve test is in progress.

2

Test Complete The valve test has completed (successfully).

3

Test Error

There was an error and the valve test could
not start.

4

Test Aborted

The valve test has been aborted.

5

Test Failure

The valve test has failed.

Table 20 Rack 10: Valve Test State descriptions

The Valve Test State is reset to 0 on the falling edge of a TEST signal.

Time 1 … Time 5 are used to report the elapsed time (in milliseconds) from the start of the test until
the feedback input state changes to the corresponding state when the Valve Test State is not 0 (Idle)
or 4 (Test Aborted). (i.e. When the feedback input state changes from state 2 to state 3, the variable
Time 3 will be updated with the time elapsed since the start of the test.)

In cases where a state is entered more than once (i.e. state 1 -> state 2 -> state 3 -> state 2), the
corresponding Time variable will only be updated for the initial entry. If a feedback state is skipped, the
corresponding Time variable will assume the same value as the next valid state (i.e. state 4 -> state 2,
so Time 3 assumes the value of Time 2). If a Time variable has a value of 0, that state was not entered
during the test.

Example:

The field device is normally closed, normally energized valve with three limit switches: open, closed,
and partial. An end of line device is used to combine the output of the limit switches into a single
voltage level, and thresholds are established so that the feedback input states are as follows:

Limit Switch State

Feedback
Input
State

Valve is
Closed

Valve is
Partially
Open

Valve is
Open

5

TRUE

FALSE

FLASE

4

FALSE

FLASE

FLASE

3

FALSE

TRUE

FALSE

2

FALSE

TRUE

TRUE

1

Open Circuit Line Fault

Table 21 Rack 10: Example - Valve Position Feedback

When the valve is closed, the feedback input state should be reported as 5. A minimal partial stroke is
desired for the valve test, so we want the valve to move just enough to change the state of the Closed
limit switch. We set ETIME to be 200ms, and ESTATE to be 4. When the test is initiated, the normally
energized valve is de-energized. After 120ms the Feedback input state changes from 5 to 4. Since
ESTATE is also 4 and we have not exceeded the 200ms time limit set in ETIME, the test has
completed successfully. All of the Time variables will be 0 except for Time 4 which will have the value
of 120.