I/o status indicators, Table 23 i/o status leds, Trusted – Rockwell Automation T8449 Trusted TMR 24V dc Valve Monitor Module - 40 Channel User Manual

Page 39: Module t8449

Advertising
background image

Trusted

TM

Module T8449

Issue 13 Apr 10

PD-T8449

39

4.3. I/O Status Indicators

There are 40 channel status indicators on the module front panel, one for each control output and one
for each feedback channel. These indicators are controlled by the FPU. The FPU receives data from
each of the module slices. The FPU performs a 2-oo-3 vote on each data bit from the slices and sets
the indicators accordingly.

The control output status indicator mode is dependent upon the numerical state of the output channel.
Each control output state can be defined to have a particular indicator mode: off, green, red, flashing
green, or flashing red.

The feedback channel status indicator mode is dependent upon the numerical state of the feedback
channel which is derived by comparing the feedback channel voltage level to a set of thresholds. Each
feedback channel state can be defined to have a particular indicator mode: off, green, red, flashing
green, or flashing red.

The configurable indicator modes allow users to customise the output status indications to suit
individual application requirements. Without customisation, the default control output indicator modes
are suitable for line-monitored digital output devices as described below:

INDICATOR STATE

DESCRIPTION

Off

Output is Off.

Green

Output is On.

Green – flashing

No Load, output open circuit.

Red

Field short circuit, output over current protection
triggered and output channel is latched off.

Red – flashing

Channel fault, or no field supply voltage

Table 23 I/O Status LEDs

The default status indicator mode for feedback channels is always off.