Rack 3: ai_mxin, Table 9 rack 3: ai_mxin descriptions, Trusted – Rockwell Automation T8449 Trusted TMR 24V dc Valve Monitor Module - 40 Channel User Manual

Page 26: Module t8449

Advertising
background image

Trusted

TM

Module T8449

Issue 13 Apr 10

PD-T8449

26

3.2.3. Rack 3: AI_MXIN

The AI_MXIN board returns the field loop voltage as well as the specific MUX data item index for the
corresponding MXDAT value for each field device.

Channel

Field
Device

Description

1

Control output voltage

2

1

MXIN value

3

Control output voltage

4

2

MXIN value

39

Control output voltage

40

20

MXIN value

Table 9 Rack 3: AI_MXIN descriptions

The voltage is the median value taken from the triplicated module. The voltage level is reported as an
integer, with the units being

1

/

500

V. This may be used directly, scaled arithmetically or scaled using the

IEC1131 TOOLSET

conversion tables.

To scale the value arithmetically simply divide the returned ‘integer’ by 500 to return the voltage as
either a REAL or INTEGER as required.

The

IEC1131 TOOLSET

conversion tables may be used to convert the value to engineering units, in this

case voltage. The full-scale range for this number format is decimal ±64, corresponding to physical
range –32000 to +32000.

The MXIN value is an integer index that defines the meaning of the MXDAT value. A complete list of
data items (i.e. valid MXIN values) is provided after the rack definitions. The MXIN value is the median
value taken from the triplicated module.