For control outputs, the State indicates the operation state of the output circuit as follows:

Value

Description

7

Channel Fault

6

Field fault (e.g. field leakage to 0V or 24V)

5

Short circuit in field wiring or load

4

Output energised (ON)

3

Open circuit in field wiring or load

2

Output de-energised (OFF)

1

No field supply voltage

0

Unused

Table 7 Rack 2: STATE Output descriptions

For feedback inputs, the State indicates the threshold voltage level of the input circuit as follows:

Value

Description

7

Channel Fault

6

Line fault, at or above maximum detectable
voltage

5

User defined voltage range

4

User defined voltage range

3

User defined voltage range

2

User defined voltage range

1

User defined voltage range

0

Line fault, at or below minimum detectable
voltage

Table 8 Rack 2: STATE Input descriptions