30 Control Group
Timing situation with Restart condition (Restart Request)
The following conditions changes the Group to “Restart Request”:
1. If any of the Alarms are on “move” - Devices such as MotorN/R/D or
Valve1,2. These Modules bring the alarm condition over the linked Bus
-chain up to the Group.
2. If the Group is in “Starting” -state and the CtrlGrp Input .PartRun is
true.
3. Or the Group is in “Running” -state and the CtrlGrp Input .AllRun
changes to false.
4. If the group is in "Starting" -state and the operator presses "Pause"
button on CtrlGrp HMI faceplate.
5. If the Group is in "Starting" -state and Starting Time Out timer times
out.