Publication RA-UM002B-EN-P - November 2010

30 Control Group

Timing situation with Restart condition (Restart Request)

The following conditions changes the Group to “Restart Request”:

1. If any of the Alarms are on “move” - Devices such as MotorN/R/D or

Valve1,2. These Modules bring the alarm condition over the linked Bus
-chain up to the Group.

2. If the Group is in “Starting” -state and the CtrlGrp Input .PartRun is

true.

3. Or the Group is in “Running” -state and the CtrlGrp Input .AllRun

changes to false.

4. If the group is in "Starting" -state and the operator presses "Pause"

button on CtrlGrp HMI faceplate.

5. If the Group is in "Starting" -state and Starting Time Out timer times

out.