E3 operational parameters – Rockwell Automation MMCL Using the Mining, Mineral, and Cement Library (MMCL) in RSLogix 5000 Appli User Manual

Page 35

Advertising
background image

Publication RA-UM002B-EN-P - November 2010

Using the E3 Module 35

E3 Operational Parameters

The following is a list of all parameters that must be set correctly in the E3. All
others that are not in this list should be left at their default value or do not take
effect with the E3p_AOI.

General Parameters

Parameter

Description

Required Setting

24

Trip enable

See graphic on page 36

25

Warning enable

See graphic on page 36

27

Single/three phase

Three phases

28

FLA setting

Full load amps from the motor nameplate

30

OL/PTC reset mode

Manual

E3 will not reset automatically

31

OL reset level

75% (default)

User will not be able to reset E3 until therm util. is

below this value.

32

OL warning level

85% (default)

E3 will show an overload warning when therm util.

is equal or above this value.

59

Output assembly

105

60

Input assembly

100

61

Assy word 0

21 (device status)

62

Assy word 1

14 (trip status)

63

Assy word 2

4 (Therm. Util.)

64

Assy word 3

9 (Average current)