QoS Guidelines

Follow these guidelines with QoS:

•

Manage the output queues based on application needs. Schedule precision
and motion control packets in the highest priority queue.

•

QoS gives preferential treatment to Industrial Automation and Control
System Network traffic at the expense of other network traffic.

•

QoS is integrated into the Stratix 8000 and Stratix 8300 switch
configurations.

•

Deploy QoS consistently throughout Industrial Automation and Control
System Network.

Resiliency

A resiliency protocol maintains parallel links for redundancy while avoiding
loops. Network convergence time is a measure of how long it takes to detect a
fault, find an alternate path, and recover from the fault:

•

During the network convergence time, some portion of the traffic is
dropped by the network because interconnectivity does not exist.

•

Communication drops if the convergence time is longer than the Logix
connection timeout.

Time Calculations in a Logix5000 System

Network convergence must occur before the control system is impacted:

•

Logix message instruction (MSG) time out (explicit, CIP Class 3)

•

I/O connection timeout (implicit, CIP Class 1), 4 x RPI, 100 ms
minimum

•

Logix Producer/Consumer connection timeout (implicit, CIP Class 1),
4 x RPI, 100 ms minimum

•

Safety I/O connection timeout (implicit, CIP Class 1), 4 x RPI (default)