Rockwell Automation Publication ENET-RM002C-EN-P - May 2013

83

Predict System Performance

Chapter 5

Performance Calculations

Logix5000 controllers use packets per second and the number of connections for
predicting system performance. However, CompactLogix 5370 controllers use
the number of Ethernet nodes to stay within their capacity for the number of
connections.

CompactLogix 5370 Controller Example

As shown in the illustration below, the 1769-L16ER-BB1B controller supports a
maximum of four nodes. Therefore, any additional node, such as a 1734 Ethernet
adapter, cannot be added to our example EtherNet/IP network. Use the
supported node chart on

page 65

and the EtherNet/IP Capacity Tool to simplify

calculating system resources for your CompactLogix 5370 network.

The devices you add directly to the local Ethernet node in the I/O configuration
section of your controller project are counted toward the 1769-L16ER-BB1B
controller’s node limitation.

45908

1769-L164ER-BB1B

1756-EN2T
1756 I/O Modules

1794-AENT
1794 I/O Modules

1734-AENT
1734 I/O Modules

PowerFlex Drive

1794-AENTR FLEX I/O Adapter

Stratix Switch

Advertising