91

Predict System Performance

Chapter 5

Determine If System Has Sufficient Bandwidth
to Meet Application Requirements

Based on the system requirements, the initial network diagram is shown below:

Chassis 1
• 1756-L73 Controller
• 1756-EN2T Module 1
• One Produced Tag

PanelView Plus Terminal

Workstation

with RSView

To Company
Intranet

Chassis 4
• 1756-EN2T Module 4
• Three Analog I/O Modules
• Three Digital I/O Modules

Chassis 7
• 1756-EN2T Module 7
• Three Analog I/O Modules
• Three Digital I/O Modules

Chassis 5
• 1756-EN2T Module 5
• Three Analog I/O Modules
• Three Digital I/O Modules

Chassis 8
• 1756-EN2T Module 8
• Three Analog I/O Modules
• Three Digital I/O Modules

Chassis 6
• 1756-EN2T Module 6
• Three Analog I/O Modules
• Three Digital I/O Modules

IMPORTANT: Each chassis with three analog and three digital I/O modules, that is, chassis 4…8, uses these connections:

• Three direct connections (one for each analog I/O module in the chassis)

• One rack connection (one for all digital I/O modules in the chassis)

Switch

Chassis 2
• 1756-L73 Controller
• 1756-EN2T Module 2
• One Consumed Tag

Chassis 3
• 1756-L73 Controller
• 1756-EN2T Module 3
• One Consumed Tag