Rockwell Automation Ethernet Design Considerations Reference Manual User Manual

Page 97

Advertising
background image

Rockwell Automation Publication ENET-RM002C-EN-P - May 2013

97

Predict System Performance

Chapter 5

Each of these controllers consumes one produced tag at an RPI = 20 ms.

Either of these EtherNet/IP modules uses these connections.

The total of 100 pps is well within the 1756-EN2T/A module’s, firmware
revision 2.003, remaining bandwidth of 9000 pps.

Recommendations to Achieve More Throughput in an Existing
Control System

Unlike the configuration of the last example control system, some control system
configurations do not initially have enough bandwidth to achieve the
desired throughput.

If you determine your control system does not have the bandwidth to achieve the
desired throughput, you need to modify your system. We recommend that you
use one of these tasks described in

step 5 on page 81

, to increase system

throughput.

EtherNet/IP Module ID:

2 or 3

Produced Tag Connections

0

= (1 + connections)/RPI

for each produced tag

=

N/A

Consumed Tags

1 tag @ 20 ms

= 2/RPI for each consumed tag

= 2/20 ms =

100

Total Packets Per Second

100