Step 6: removing the old emi-protection plate – Rockwell Automation 20D PowerFlex 700S and H Fan Inverter Upgrade Kit (Frame 9) User Manual

Page 12

Advertising
background image

12

Rockwell Automation Publication PFLEX-IN015A-EN-P - March 2005

PowerFlex 700S and 700H Fan Inverter Upgrade Kit (Frame 9)

Step 6: Removing the Old
EMI-Protection Plate

Task

Description
Disconnect the external cables, which connect the drive to incoming AC power and
the motor, from the power terminal block.

Disconnect the internal cables from the power terminal block and place them at the
top of the drive, in order to gain access to the EMI-Protection Plate.
Proper tightening torque for reassembly is 20 N•m (177 lb•in).
Remove four M4x8 Pozidrive screws, which secure the EMI-Protection Plate to the
drive.
Proper tightening torque for reassembly is 3 N•m (27 lb•in).
Remove the two screws, which secure the common mode inductors. Then remove
the inductors.
Proper tightening torque for reassembly is 3 N•m (27 lb•in).
Disconnect the fan which is mounted on the EMI-Protection Plate. You may need to
remove the fan on the new EMI Plate to rotate it. If you do, the proper tightening
torque for reassembly is 3 N•m (27 lb•in).
Remove the EMI-Protection Plate from the drive.

A

B

C

D

E

F

B

B

EMI
Protection
Plate

C

C

C

C

D

D

E

Advertising
This manual is related to the following products: