Complex i/o equipment definition, I/o complex equipment ‘ttmrp, I/o complex equipment – Rockwell Automation T8110B/T8110 Trusted TMR Processor User Manual

Page 18: Ttmrp, Trusted

Advertising
background image

Trusted

TM

TMR Processor T8110B/T8110

Issue 18 Feb 08

PD-T8110B/T8110

18

3.2. Complex I/O Equipment Definition

All Trusted

TM

systems require a processor definition in the I/O Connection Table. Details of how to edit

the I/O Connection table are given in PD-8082B. The structure of the definition is given below.

3.2.1. I/O Complex Equipment ‘TTMRP’

Description:

Trusted

TM

TMR Processor. This definition will open a single TMR Processor module.

Only one installation is allowed. The data attached will give the application access to
the user LEDs, real time clock and external analogue data from the system.

OEM PARAMETERS

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 15
0

The TICS chassis & slot number where the TMR Processor module is
placed.

CONFIGURATION

PHYSICAL MODULE:

RACK 1: [TTMRP_0]

16 ANALOGUE Inputs

Channel 1:

Module temperature (tenths of degrees C)

Channel 2

24V dc feed 1 after protection diodes (mV)

Channel 3

24V dc feed 2 after protection diodes (mV)

Channel 4

FRCA 8V dc supply (mV)

Channel 5

FRCB 8V dc supply (mV)

Channel 6

FRCC 8V dc supply (mV)

Channel 7

16-bit scan count

Channel 8

16-bit scan count

Channel 9

Number of locked variables in the application

Channels 10 – 16

Reserved

RACK 2: [TTMRP_1]

16 BOOLEAN Inputs

Channel 1

PSU-A Output Status TRUE = Fail, FALSE = Pass

Channel 2

PSU-B Output Status TRUE = Fail, FALSE = Pass

Channel 3

PSU-A Line Status TRUE = Low Voltage Warning, FALSE = OK

Channel 4

PSU-B Line Status TRUE = Low Voltage Warning, FALSE = OK

Channel 5

IRIG Input Status TRUE = Pass, FALSE = Fail

Channel 6

System Health TRUE = Fail, FALSE = Healthy

Channel 7

Reset Pushbutton Status TRUE (one-shot) = pressed

Channel 8

Keyswitch Status TRUE = Run, FALSE = Maintain

Channel 9 - 16

Not used

RACK 3: [TTMRP_2]

16 BOOLEAN outputs

Channel 1

This channel drives the USER LED 1.
TRUE = USER LED 1 ON, FALSE = USER LED 1 OFF

Channel 2

This channel drives the USER LED 2.
TRUE = USER LED 2 ON, FALSE = USER LED 2 OFF

Channel 3

Unlock all channels, edge triggered on a (FALSE -> TRUE) change

Channel 4

System Healthy LED controls. TRUE = Unhealthy, FALSE = Healthy.

Channel 5

USER LED 1 Colour. TRUE = Green, FALSE = Red.

Channel 6

USER LED 2 Colour. TRUE = Green, FALSE = Red.

Channels 7 – 16

Not used