4.6.1. Reset Button

The fault Reset button clears all recorded faults, resets all fault counters and requests all modules to
do the same. Fault testing continues, and faults that are still present will be recorded again. The fault
reset can also be initiated from the Engineering Workstation by personnel who are authorised by the
appropriate passwords, to implement maintenance changes to a Trusted

TM

System.

Note that although pressing the Reset button will make the system look healthy, it may erase faults that
take many hours to be recorded again. It is recommended to note the fault code (which appears at the
bottom of the HKEEPING board in each module’s complex equipment definition, see the module PD
and PD-8032B) before pressing Reset.

4.6.2. Maintenance Enable Keyswitch

The two position keyswitch is used to select the following modes:

In the ‘Run’ position: the memory is locked.

In the ‘Maintenance’ position: the keyswitch allows the download of application programs by the
Engineering Workstation, together with the appropriate access permission.

Note To prevent unauthorised use, the key can be removed with the keyswitch in either position.

4.7.

Composite Scan Time Estimation (pre TÜV release 3.5)

The composite scan time for a Trusted

TM

system represents the time required to read the input data,

solve the application logic, and write the output data. This sequence is repeated cyclically for as long
as the Trusted

TM

system is executing an application. For convenience, the above cyclical sequence is

broken down into four discrete elements: central modules, input modules, output modules, and the
application. The estimated composite scan time is the sum of those four elements.

The calculations here apply to systems before TÜV release 3.5. At release 3.5 the execution times
have been significantly improved. For systems from release 3.5, refer to section 4.8.

4.7.1. Central Modules

The Central Module time is based on the number and type of central Trusted

TM

modules. It is

calculated by multiplying the number of installed modules by the appropriate time factor, then adding
the results.

Module Type

No. Installed

Time

Standby TMR Processor Module

x 4 ms

TMR Interface Module

x 15 ms

Communications Interface Module

x 4 ms

Central Module Total

Run
Maintenance