Safety Function: Hinge Switch

3

Rockwell Automation Publication SAFETY-AT096A-EN-P – November 2013

General Safety Information

Contact Rockwell Automation to find out more about our safety risk assessment

services.

IMPORTANT

This application example is for advanced users and

assumes that you are trained and experienced in safety

system requirements.

ATTENTION: Perform a risk assessment to make sure all

task and hazard combinations have been identified and

addressed. The risk assessment can require additional

circuitry to reduce the risk to a tolerable level. Safety circuits

must take into consideration safety distance calculations,

which are not part of the scope of this document.

Table of Contents

Important User Information ....................................................................................... 2
General Safety Information ....................................................................................... 3
Introduction ............................................................................................................... 3
Safety Function Realization: Risk Assessment ......................................................... 3
Hinge Interlock Switch Safety Function ..................................................................... 4
Safety Function Requirements .................................................................................. 4
Functional Safety Description ................................................................................... 5
Bill of Material ........................................................................................................... 5
Setup and Wiring ...................................................................................................... 6
Configuration ............................................................................................................ 7
Calculation of the Performance Level ........................................................................ 8
Verification and Validation Plan ............................................................................... 11
Additional Resources .............................................................................................. 16

Introduction

This application technique explains how to wire and configure an Ensign 3 hinge

interlock switch and an E-stop as input devices, with a Guardmaster

®

dual-input

safety relay (GSR DI) as the logic control and two 100S safety contactors as the

output devices to create an integrated safety system.

Safety Function Realization: Risk Assessment

The required performance level is the result of a risk assessment and refers to the

amount of the risk reduction to be carried out by the safety-related parts of the

control system. Part of the risk reduction process is to determine the safety functions

of the machine. In this application, the performance level required (PLr) by the risk

assessment is Category 3, Performance Level d (CAT. 3, PLd), for each safety

function. A safety system that achieves CAT. 3, PLd, or higher, can be considered

control reliable. Each safety product has its own rating and can be combined to

create a safety function that meets or exceeds the PLr.