8

Safety Function: Hinge Switch

Rockwell Automation Publication SAFETY-AT096A-EN-P – November 2013

Configuration

The following procedure sets the function of the device.

1. To start configuration/overwrite: with the power off, turn the rotary switch to

position 0.
The unit powers up. After the power-up test, the PWD LED flashes red.

2. To set the configuration, turn the rotary switch to position 2.

The IN 1 LED blinks for the new setting.
Position is set when the PWR LED is solid green.

3. Lock-in the configuration by cycling unit power.
4. Confirm the configuration before operation.
5. Record the unit setting in the white space on the face of the device.

LOGIC 2 = L12 or (IN1 and IN2)






Calculation of the Performance Level

When properly implemented, the two safety functions of this safety system,

prevention of access of hazardous motion in the guarded area, and emergency stop

of hazardous motion initiated by an E-stop button, can achieve a safety rating of

Category 3, Performance Level d (CAT. 3, PLd), according to EN ISO 13849-1, as

calculated using the SISTEMA software PL calculation tool.
.



LOGIC